Linear reflective smoke detector, 400 and 500 line
Mod. 1043/209
SKU: 1043/209
The linear smoke detector is particularly suitable for satisfying applications in the field of cultural heritage protection, such as: museums, churches, historic buildings, art exhibitions, etc.
Its operating principle is based on the interaction between the smoke present in an environment generated by the beginning of a fire and an infrared ray emitted and reflected by a special optical reflector.
• Supply voltage: 10.8 ÷ 26.8 Vdc
• Quiescent consumption at 24 Vdc: 55 mA
• Quiescent consumption at 12 Vdc: 45 mA
• Consumption in alarm at 24 Vdc: 50 mA
• Consumption in alarm at 12 Vdc: 40 mA
• Consumption in fault at 24 Vdc: 35 mA
• Consumption in fault at 12 Vdc: 30 mA
• Pre-alarm dimming thresholds: 20%, 25%, 30%, 35%
• Alarm blackout threshold: 35%
• Minimum operating distance: 5 m
• Maximum operating distance: 100 m
• Transmitter beam wavelength: 890 mm
• Beam misalignment tolerance: ±1°
• Pre-alarm relay 1A, 30Vdc resistive load - NO/NC contact selectable via jumper
• Alarm relay 1A, 30Vdc resistive load - NO/NC contact selectable via jumper
• Fault relay 1A, 30Vdc resistive load - NO/NC contact selectable via jumper
• Conventional line - input voltage range: 10 ÷ 20Vdc
• Conventional line - pre-alarm absorption: 20 mA @ 20Vdc
• Conventional line - alarm absorption: 40 mA @ 20Vdc
• Conventional line - reset pulse duration: 200 mS
• Operating temperature: (-10 ± 3) °C ÷ (55 ± 2) °C
• Relative humidity: (93 ± 3) %
• Degree of protection: IP55
• Weight: 900 g
• Dimensions (W x H x D): 248 x 122 x 120 mm
24 month warranty