Shipping
Shipping in 7-10 business days
Description
COsensor ZafirCO addressable carbon monoxide detection control panel
SKU: ZCO325
Features
• COsensor ZafirCO addressable 3-zone carbon monoxide detection control panel with 25 CO detectors + 25 NO2 detectors per zone
• Designed in accordance with European standard EN 50545-1 and certified to UNE 23300.
Specifications
Description
Automatic COsensor addressable control panel with diffusion sensors for carbon monoxide (CO) and nitrogen dioxide (NO2), designed in accordance with European standard EN 50545-1 and certified to UNE 23300.
3-zone control panel with capacity for up to 25 CO sensors and/or 25 NO2 sensors per zone.
The COsensor ZafirCO control panel allows the alarm activation concentration to be configured.
It has independent volt-free contact outputs for each zone for every ventilation and alarm level, as well as a general fault output and a 30V DC auxiliary power supply.
The control panel has a maintenance mode that makes it easy to check sensor operation by observing how their LEDs flash when exposed to test gas.
The control panel can identify all sensors in the installation via the menu using their programming numbers. When identification is not required, the control panel's auto-configuration function automatically detects all sensors in the zones and displays them. Once this information is confirmed, the control panel enters operating mode directly.
The equipment's operating philosophy and mode are designed in accordance with EN 50545-1, using diffusion sensors with factory calibration for operation throughout their service life, and are UNE 23300 certified.
Features
• 3-zone ventilation control panel with COsensor brand diffusion sensors, models SCO (CO sensor) and SDN (NO2 sensor)
• Volt-free contact output (COM/NO) for ventilation 1, ventilation 2 (DVB models only) and alarm
• Fault output with volt-free contacts (COM/NO/NC)
• 30V DC, 1A auxiliary power output
• Concentration readings averaged in accordance with EN 50545-1 for up to 60 minutes
• Alarm level selectable from 5 to 300 ppm of CO and from 0.1 to 30 ppm of NO2
• Alarm activation delay and alarm stop delay selectable from 0 to 5 minutes
• Maintenance mode to check sensor operation
• 4-line, 40-character backlit LCD display
• Dimensions: 418 x 324 x 150 mm
• System designed in accordance with European standard EN 50545-1
• UNE 23300 certified system
24-month warranty
eb: 227319881415