Description
Conventional relay module for fire detection systems
SKU: MDL1R
Features
• Cofem 1-relay module for fire detection systems
• Unsupervised NO/NC volt-free contact
• 2A safety fuse
• Mounted on a plastic base
• Easy to install
• Installation using a plastic base with adhesive strips
Specifications
Technical specifications
• COFEM conventional relay module for fire detection systems
• 1 relay with unsupervised volt-free NO (Normally Open) and NC (Normally Closed) outputs
• Supply voltage: 24-35V
• Active consumption: 20mA
• Standby consumption: 0mA
• Contact rating: 30Vdc / 230Vac 2A
• 2A safety fuse on the volt-free contact side
Functionality
• Controls electromagnets for fire doors and fire shutters in conventional systems
• Easy installation using a plastic base with adhesive strips
• Installed in control panels or external power supply units (FAE), making use of the available space
Power supply
• Powered by the fire alarm control panel or an external power supply unit (FAE)
Physical characteristics
• Plastic base for mounting with adhesive strips
Contents
• COFEM-117 conventional relay module (MDL1R)
24-month warranty