Shipping
Shipping in 7-10 business days
Description
2-zone extinguishing control panel
SKU: CLVR02EXT
Features
Cofem fire extinguishing control panel
• 2 conventional system zones
• Certified to EN 54-2/4 and EN 12094-1
Specifications
Specifications
• 2-zone control panel with extinguishing functionality for use with conventional detectors and call points
• Third additional zone, configurable as a fire detection and alarm zone for conventional detectors and call points, or as a monitoring input for an external fire protection system
• 2 general sounder outputs, 1 alarm output, 1 fault output, 2 30V DC outputs, test mode, threshold configuration, metal enclosure, etc.
• Normal mode: Extinguishing pre-warning output R1 activates when Zone 1 or Zone 2 is in alarm state
• Sequential mode: Output R1 activates intermittently (1s with Zone 1 or Zone 2 in alarm state, 0.5s with Zones 1 and 2 in alarm state, and continuously once the extinguishing output R2 delay has elapsed)
• Simultaneous mode: Output R1 activates when Zones 1 and 2 are in alarm state
• 1 extinguishing stop button and 1 extinguishing activation button on the control panel
• Manual stop and extinguishing activation buttons can be installed in the flooding zone
• 1 supervised extinguishing output (designated "R2"), with a delay adjustable from 0 to 60s and protected by a resettable fuse
• Reset release delay after activation of the extinguishing system, programmable from 0 to 30 minutes
• Modbus protocol with RS485 output available on request
• Online PC software available using the Modbus feature
• Contact ID on request
• Certified to EN 54-2, EN 54-4 and EN 12094-1, with CE marking
24-month warranty
eb: 236784165949