FAAST-LT P/ analogue loop aspiration system, 1 channel/2 detectors
SKU: FL2012EI-HS
Features
• FAAST-LT P/ analogue loop aspiration system, 1 channel/2 detectors
• Compatible with AM-8200 control panel
Specifications
FAAST-LT single-channel aspirating smoke detection system / IP65, with direct connection to the AM-8200 loop, model FL2012EI-HS, featuring a built-in isolator and local supervised sounder output per channel. Includes an addressable control module (01-159) on the door to monitor power supply and/or flow faults, and two VIEW point detectors with 9 alarm levels and pre-alarm sensitivity settings configurable from the analogue fire alarm control panel.
System information via a pendulum-style graphic bar with 9 airflow levels to verify that airflow meets EN54-20 requirements.
• Internal point detectors with manual and automatic test functions and decimal addressing (01-159), easily replaceable.
• Internal log of 2,244 events.
• Dust discrimination principle using AWACS algorithms.
• Includes an easily accessible internal filter (FL-IF) and an ultrasonic flow sensor.
• Configured via a standard USB cable and PipeIQ LT software (included).
• Compatible with OPAL protocol 159+159 (displays speed/flow values per channel).
• Features 2 sampling pipe inlets per channel. Maximum length: 50 m each, in a single 100 m line, and 160 m in a T configuration, with up to 18 orifices per channel in Class C, 6 in Class B and 3 in Class A.
• Requires a 24 Vdc power supply in accordance with EN54-4.
• Maximum current consumption: 360mA at 24 Vdc (without sirens); supplied with PipeIQ LT design and configuration software.
24-month warranty
eb: 225559712290